● Altitude up to 2000m;
● Ambient medium temperature should be within -5℃ to +40℃ (+45℃ for marine products);
● It can withstand the effect of damp air;
● It can withstand the effect of moulds;
Описание
Ambient and Installation Conditions
● Altitude up to 2000m;
● Ambient medium temperature should be within -5℃ to +40℃ (+45℃ for marine products);
● It can withstand the effect of damp air;
● It can withstand the effect of moulds;
● It can withstand the effect of nuclear radiation;
● The max inclination is 22.5℃.
● It still can work reliably when the ship subjects to normal vibration;
● It can still work reliably if the product subjects to the earthquake (4g).
● Places where the surrounding medium is free from explosion danger, and far away from gas or conductive dust that would erode the metal or destroy the insulation;
● Keep away from rain or snow.
Components of Circuit Breaker
Product Selection Guide
QM1 | 125 | C | P | 4 | |||
Product code | Frame size | Current class | Code of control circuit source voltage | Pole number | |||
Moulded-case circuit breaker | 125 160 250 400 630 800 Note: 125 is upgraded type of 63 frame 160 is upgraded type of 100 frame 250 is upgraded type of 225 frame 630 is upgraded type of 400 frame | C | S | H | P: electric operation Z: rotary handle W: direct operation | 3: 3-pole 4: 4-pole | |
125 | 15/10 | 18/15 | 25/18 | ||||
160 | 20/15 | 25/18 | 35/25 | ||||
250 | 20/15 | 25/18 | 35/25 | ||||
400 | 35/25 | 50/35 | |||||
630 | 35/25 | 50/35 | |||||
1250 | 50/35 | 65/50 |
300 | 125A | 2 | A | |
Release type and internal accessory | Rated current (A) | Application | Code of four-pole product | |
The first digit represents release type 2: Has instantaneous release only 3: Complex release Note: Later two digits are the code of accessories (see accessory table) | 125 | 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 | 1: power distribution 2: motor protection | A: N-pole without protection cannot close or open B: N-pole without protection can close and open C: N-pole with protection can close and open D: N-pole with protection cannot close or open |
160 | 63, 80, 100, 125, 140, 160 | |||
250 | 100, 125, 140, 160, 180, 200, 225, 250 | |||
400 | 250, 300, 315, 350, 400 | |||
630 | 400, 500, 630 | |||
1250 | 500, 630, 700, 800,1000,1250 |
Q1 | D1 | Q | 2 | |||
Accessory voltage | Electric operation voltage | Installation methods | Install wiring board or not | |||
Under-voltage release | Shunt release | Auxiliary alarm | DC1 Electric Operation | DC3 Electric Operation | Q: Front-board H: Back-board C: Plug-in type | 1: No 2: Yes |
Q1: AC220V | F1: AC220V | J1: AC125V | D1: AC220V | D5: AC230V | ||
Q2: AC240V | F2: AC380V | J2: AC250V | D2: AC230V | D6: AC110V | ||
Q3: AC380V | F3: DC110V | J3: DC125V | D3: AC380V | D7: DC220 | ||
Q4: AC415V | F4: DC24V | J4: DC24V | D4: AC400V | D8: DC110 | ||
D9: AC110-240V | ||||||
D10: DC100-220V | ||||||
Note: Adaptable voltages for two electric operations. Please refer to the introduction of external accessory. | ||||||
Main Performance Indexes
Frame current (A) | 125 | 160 | |||||
Model | QM1-125C | QM1-125S | QM1-125H | QM1-160C | QM1-160S | QM1-160H | |
Pole number | 1, 2, 3, 4 | 2, 3, 4 | |||||
Rated current (A) | 10, 16, 20, 32, 25, 40, 50, 63, 80, 100, 125 | 63, 80, 100, 125, 140, 160 | |||||
Rated voltage (V) | AC400V | AC400V | |||||
Rated insulation voltage (V) | AC1000V | AC1000V | |||||
Short-circuit breaking capacity(KA)Icu/Ics | AC400V | 15/10 | 18/15 | 25/18 | 25/10 | 25/18 | 35/25 |
Operating cycle number | Electrical life | 6000 | 3000 | ||||
Mechanical life | 9000 | 7000 | |||||
Outline dim(mm) a-b-c-ca | 1P | 25-130-68-90 | - | - | - | ||
2P | 50-130-68-90 | 60-155-68-90 | 60-155-68-90 | 60-155-88-115 | |||
3P | 75-130-68-90 | 90-155-68-90 | 90-155-68-90 | 90-155-88-115 | |||
4P | 100-130-68-90 | 120-155-68-90 | 120-155-68-90 | 120-155-88-115 | |||
Weight (kg) | 1P | 0.32 | - | - | - | ||
2P | 0.5 | 0.55 | 1 | 1.1 | |||
3P | 0.55 | 0.65 | 1.1 | 1.2 | |||
4P | 0.65 | 0.8 | 1.4 | 1.5 | |||
Electric operating device (MD) | ● | ||||||
External driving operating handle | ● | ||||||
Automatic release | Thermal electromagnetic type |
Frame current (A) | 250 | 400 | |||||
Model | QM1-250C | QM1-250S | QM1-250H | QM1-400S | QM1-400H | ||
Pole number | 3, 4 | 3, 4 | |||||
Rated current (A) | 100, 125, 140, 160, 180,200, 225, 250 | 250, 315, 350, 400 | |||||
Rated voltage (V) | AC400V | AC400V | |||||
Rated insulation voltage (V) | AC1000V | AC1000V | |||||
Short-circuit breaking capacity(KA)Icu/Ics | AC400V | 25/15 | 25/18 | 35/25 | 35/25 | 50/35 | |
Operating cycle number | Electrical life | 3000 | 2000 | ||||
Mechanical life | 7000 | 4000 | |||||
Outline dim(mm) a-b-c-ca | |||||||
3P | 105-165-68-92 | 105-165-88-115 | 140-257-103-155 | ||||
4P | 140-165-68-92 | 140-165-88-115 | 184-257-103-155 | ||||
Weight (kg) | |||||||
2P | 1.5 | 1.7 | 5.5 | ||||
3P | 1.9 | 2.1 | 7 | ||||
Electric operating device (MD) | ● | ||||||
External driving operating handle | ● | ||||||
Automatic release | Thermal electromagnetic type |
Frame current (A) | 630 | 1250 | |||||
Model | QM1-630S | QM1-630H | QM1-800S | QM1-1250H | |||
Pole number | 3, 4 | 3, 4 | |||||
Rated current (A) | 250, 315, 350, 400, 500, 630 | 500, 630, 700, 800,1000,1250 | |||||
Rated voltage (V) | AC400V | AC400V | |||||
Rated insulation voltage (V) | AC1000V | AC1000V | |||||
Short-circuit breaking capacity(KA)Icu/Ics | AC400V | 35/25 | 50/35 | 50/35 | 65/50 | ||
Operating cycle number | Electrical life | 2000 | 1500 | ||||
Mechanical life | 4000 | 4000 | |||||
Outline dim(mm) a-b-c-ca | |||||||
3P | 140-257-103-155 | 210-275-103-155 | |||||
4P | 184-257-103-155 | 280-275-103-155 | |||||
Weight (kg) | |||||||
2P | 5.7 | 9.5 | |||||
3P | 7.5 | 12.5 | |||||
Electric operating device (MD) | ● | ||||||
External driving operating handle | ● | ||||||
Automatic release | Thermal electromagnetic type |